Sunday September 5, 2010   

Model LP2000I Electronic Circuit Breaker Interface

Tech Bulletin: T990212

Model LP2000I Electronic Circuit Breaker Interface

The Model LP2000I Interface provides a means to monitor and control the Line Power Electronic Circuit Breaker on the Pyott-Boone monitoring system. The device screen on the monitoring system will indicate the status of the unit, as well as operating and leakage currents. Statuses include whether the LP 2000 unit is tripped, open (reset) or closed (engaged).

The LP2000I Interface has two different configurations. The first configuration is for the 320-baud Pyott-Boone Monitoring System which includes a LP2000I Interface and a Model 1750A Fiber Optic Link. The two devices connect together with a fiber link to isolate the power center electrical equipment from the monitoring system. The second configuration has an LP2000I Interface connected to a Model 1760 Fiber Optic Link. This configuration is used on 4800-baud Pyott-Boone monitoring systems. Both configurations require the LP 2000 Circuit Breaker to have an RS-485 data line system that uses the Modbus RTU standard. Each LP2000I Interface can operate up to four LP 2000 Circuit Breakers on the same RS-485 line. 

 

Model LP2000I Features:

Power: 120 VAC

Enclosure: Non-metallic high impact molded plastic. Rated NEMA 1,3,3S,4,4X,12,13

Communications: PBE 320 Baud or 4800 Baud